Accurate Fault Location Algorithm on Power Transmission Lines with use of Two-end Unsynchronized Measurements

Main Article Content

Dine Mohamed
Sayah Houari
Bouthiba Tahar

Abstract

This paper presents a new approach to fault location on power transmission lines. This approach uses two-end unsynchronised measurements of the line and benefits from the advantages of digital technology and numerical relaying, which are available today and can easily be applied for off-line analysis. The approach is to modify the apparent impedance method using a very simple first-order formula. The new method is independent of fault resistance, source impedances and pre-fault currents. In addition, the data volume communicated between relays is sufficiently small enough to be transmitted easily using a digital protection channel. The proposed approach is tested via digital simulation using MATLAB and the applied test results corroborate the superior performance of the proposed approach.

Article Details

Section
Articles